Addendum to Regional Water Supply Facilities Plan Final Report (April 2011) Page: 7-9
256 p. : ill. ; 28 cm.View a full description of this report.
Extracted Text
The following text was automatically extracted from the image on this page using optical character recognition software:
APRIL 2011
8
WASTE FROM WATER TREATMENT PROCESS
PLANT SIZE # OF
CAPACITY PUMPS
3 MGD 2100 GPM 2 SLUDGE DRYING BED
WASTE SOURCE 5 MGD 3500 GPM 2 (CONCRETE, EXP. TO AIR)
1 OF 2 . 10 MGD 7000 GPM 2
15 MGD 7000 GPM 3
FILTER BACKWASH HOLDING
V=30,000 CF BED SIZE (IN FEET)
FROM FILTER PLANT WIDTH LENGTH DEPTH # OF
WASTE SOURCE B WAH12" CAPACITY BEDS
2 OF 2 .. 12" PIPE 3 MGD 20 150 6 2
PIPE 5 MGD 20 150 6 3
10 MGD 20 150 6 6
NUMBER OF SLUDGE HOLDING/RECYCLING BASIN 15 MGD 20 150 6 9
60' X 60'X 10' EACH (EXP. TO AIR SOIL LINING)
HOLDING FOR ALL FILTER
(CONCRETE) PUMP=25000 BACKWASH AND SEDIMENTATION
HOLDING AU CYCL GPM @ ' WASTE FOR 1 MAX DAY
BACKWASH CYCLESSLUDGE HOLDING/RECYCLING BASIN
D
CHC
B A
SLUDGE HOLDING/RECYCLING SIZE (IN FEET)
PLANT A B C D # OF TOTAL
CAPACITY TANKS VOLUME CF3 MGD 40 100 85 125 1 1 . 55000
BACK TO SLUDGE
HOLDING/RECYCLE
DRY SLUDGE PUMPPLANT SIZE # OF
CAPACITY PUMPS
3 MGD 1500 GPM 2
5 MGD 3000 GPM 2
10MGD 3500 GPM 3
.5 MGD 5500 GPM 45 MGD 40 100 1001401 1 Z 62:000
10 MGD 40 100 1357 7505 20 1,000
15 GD j0 10 75 15 1J040JC0D.1 HIDALGO COUNTY
DRAINAGE DISTRICT CONCEPTUAL PLANT PROCESS TRAIN FOR A DMF+NF
NO. 1., iCivil Systems.
SE Enginering, Inc.
9894 8# .onn baet. Suita404
- Houston, Texas 77036
(713)7823811 (713) 782-3812 (Fax)
FIRM REG. #5248Figure 7-3-3. Conceptual WTP Process Train for Alternative C - ACTIFLO + DMF + NF
REGIONAL WATER SUPPLY FACILITIES PLAN
SCALE: N.T.S.
-
7-9
Upcoming Pages
Here’s what’s next.
Search Inside
This report can be searched. Note: Results may vary based on the legibility of text within the document.
Tools / Downloads
Get a copy of this page or view the extracted text.
Citing and Sharing
Basic information for referencing this web page. We also provide extended guidance on usage rights, references, copying or embedding.
Reference the current page of this Report.
Civil Systems Engineering, Inc. Addendum to Regional Water Supply Facilities Plan Final Report (April 2011), report, May 2011; Houston, Texas. (https://texashistory.unt.edu/ark:/67531/metapth839161/m1/213/: accessed July 16, 2024), University of North Texas Libraries, The Portal to Texas History, https://texashistory.unt.edu; crediting UNT Libraries Government Documents Department.